PERFORMANCE DATA
SM TQDCI 1-A.1 GB
5.4 FLO 12 DCI
5.4.1 Cooling Capacity Factors - Unit A,B,C or D
230[V] : Indoor Fan at High Speed.
ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC]
OD COIL
ENTERING AIR DB
TEMPERATURE [ºC]
DATA
22/15 24/17 27/19 29/21 32/23
-10 - 20
(protection range)
TC 80 - 110 % of nominal
SC 80 - 105 % of nominal
PI 25 - 50 % of nominal
25
TC 0.97 1.03 1.09 1.16 1.22
SC 1.01 1.03 1.05 1.07 1.09
PI 0.79 0.80 0.82 0.83 0.85
30
TC 0.92 0.98 1.05 1.11 1.17
SC 0.98 1.00 1.03 1.05 1.07
PI 0.88 0.89
0.91
0.92 0.94
35
TC 0.87 0.94
1.00
1.06 1.13
SC 0.96 0.98 1.00 1.02 1.04
PI 0.97 0.99
1.00
1.02 1.03
40
TC 0.83 0.89
0.95
1.02 1.08
SC 0.93 0.95 0.97 1.00 1.02
PI 1.06 1.08 1.09 1.11 1.12
46
TC 0.77 0.83 0.90 0.96 1.02
SC 0.90 0.92 0.94 0.96 0.99
PI 1.17 1.19 1.20 1.22 1.23
LEGEND
TC Total Cooling Capacity, kW
PI Power Input, kW
WB Wet Bulb Temp., (
o
C)
DB Dry Bulb Temp., (
o
C)
ID Indoor
OD Outdoor
5.4.2 Capacity Correction Factors
27/19
22/15
24/17
29/21
32/23
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
1.4
20 25 30 35 40 45 50
Outdoor Temperature [deg C]
Capacity Ratio