TROUBLESHOOTING
SM CINCO 1-A.1 GB
13.2 General System Failures and Corrective Actions
SYMPTOM / PROBLEM PROBABLE CAUSE CORRECTIVE ACTION
Indoor unit
1
Indoor unit power supply
indicator (Red LED) does
not light up.
No Power supply
Check supply voltage to main terminals L and N with volt
meter.
Miss-wiring
Check all supply wiring to controller and terminals
according to wiring diagram
Loose connection Check all power wiring connections
Display and display
cable
Check continuity of each wire of the display wires/pins
with Ohm meter
If still not OK Check if fuse burnt
2
Fuse burned in indoor unit
controller
Short Circuit between
wires
Check for any cuts or exposed supply wires or miss-
wiring
Failure of Indoor Unit
Fan Motor
Check the motor and capacitor ( 13.5.19)
Check for any cuts or exposed wires
If still not OK Replace fuse
3
Indoor unit does not respond
to remote control message
Remote control
message not reached
the indoor unit
Check remote control batteries
Check continuity of each wire of the display wires/pins
with Ohm meter
If still not OK Replace display box or indoor Electronic Assembly
4
Indoor unit responds to
remote control message but
Operate indicator (Green
LED) does not light up
Problem with display
PCB
Replace display PCB.
If still not OK Replace indoor Electronic Assembly
5
Indoor fan does not start
(louvers are opened and
Green LED is ON)
Unit in heat mode and
coil is still not warm
Change to Cool or Fan mode
Failure of Indoor Unit
Fan Motor
Check the motor and capacitor ( 13.5.19)
Check for any cuts or exposed wires
Problem with controller
or motor capacitor
Change to high speed and Check power supply to motor
is higher than 220VAC
If still not OK Replace indoor Electronic Assembly
6
Indoor fan works when
unit is OFF, and indoor fan
speed is not changed by
remote control command.
Controller problem Replace indoor Electronic Assembly
7
Water leakage from indoor
unit
Indoor unit drainage
tube is blocked
Check and open drainage tube
8
One indoor unit or more are
operating in cool mode with
no capacity, and the other
units have water leaks/
freezing problems
The communication
wires of the indoor
units are switched
Check and correct the communication wires connection
9
One indoor or more are
operating in heat mode with
a limited capacity, and the
coil on the other units are
very hot.
Outdoor unit
10
Outdoor unit display board
and LEDs are off
No power supply
Check supply voltage to main terminals L and N with volt
meter.
Miss-wiring
Check all supply wiring to controller and terminals
according to wiring diagram
Loose connection Check all power wiring connections
Burnt fuse Check fuse on the main board ( 13.5.5)
If still not OK Replace main board (14.1.13)