Airwell BS 12 DCI Manuel de service Page 8

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 62
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 7
2-3
PRODUCT DATA SHEET
2.2.3
K 9 DCI Specifications
Model Indoor Unit / Type K 9 DCI / Cassette
Installation Method FLARE
Fan Motor Output W 36
Power Supply V/Ph/Hz 220-240 / 1/ 50
INDOOR
Fan Type & Quantity Centifugal *1
Airflow
(2)
Cooling / Heating
H/M/L m
3
/hr 530/600 500/530 435/450
Sound Power Level
(3)
Cooling / Heating
L - H dB (A) 42-48 / 42-47
Sound Pressure Level
(4)
Cooling / Heating
L - H dB (A) 32-38 / 32-37
Condensate Drain Tube I.D. mm 16
Dimensions W/H/D mm 571 287 571
Weight kg 22.7
Package Dimensions W/H/D mm 685 415 685
Stacking Height Units 5
Heating Elements kW N/A
Moisture Removal L/hr 1
2.2.4 K 12 DCI Specifications
Model Indoor Unit / Type K 12 DCI / Cassette
Installation Method FLARE
Fan Motor Output W 36
Power Supply V/Ph/Hz 220-240 / 1/ 50
INDOOR
Fan Type & Quantity Centifugal *1
Airflow
(2)
Cooling / Heating
H/M/L m
3
/hr 580/620 510/560 435/450
Sound Power Level
(3)
Cooling / Heating
L - H dB (A) 42-49 / 42-48
Sound Pressure Level
(4)
Cooling / Heating
L - H dB (A) 32-38 / 32-38
Condensate Drain Tube I.D. mm 16
Dimensions W/H/D mm 571 287 571
Weight kg 24.4
Package Dimensions W/H/D mm 685 415 685
Stacking Height Units 5
Heating Elements kW N/A
Moisture Removal L/hr 1.5
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN14511.
(2) Airflow in ducted units; at nominal external static pressure.
(3) Sound power in ducted units is measured at air discharge.
(4) Sound pressure level measured at 1 meter distance from unit.
Vue de la page 7
1 2 3 4 5 6 7 8 9 10 11 12 13 ... 61 62

Commentaires sur ces manuels

Pas de commentaire