CONTROL SYSTEM
SM YAZDCI 1-A.1 GB
ANY
0
ON
NLOAD
PUMP
OFF
ON
OPER
LED
OFF
Overflow
Water Level
Normal
BLINK
NLOAD is
forced to 0
8 min 8 min
Overflow when
unit is ON
Overflow when
unit is OFF
8 min
11.6 Installation Test Mode
11.6.1 Test Objectives
Find tube-communication wires mismatch. 
Instruct the technician to match the tubes to the communication wires.
Find EEV or tubing problems.
11.6.2 Test Concept
The unit will open each EEV separately in cooling mode.
Detect a temperature drop on the indoor unit.
Based on the temperature drop, the system can match the tube to the indoor unit.
11.6.3 Test Rules
Before starting the installation/technician test, make sure for the following:
No indoor communication channel is connected to non existing tube channel.1.
The number of the connected/installed indoor unit is set properly.2.
All the EEVs are connected properly to the right EEV channels.3.
No mix between the indoor unit’s tubes, each indoor unit must have its own tubes connected 4.
properly to the outdoor unit.
If the rules above are not respected, the test results will make no sense.