12-1
TROUBLESHOOTING
SM YAZDCI 1-A.1 GB
12. TROUBLESHOOTING
WARNING!!!
When Power Up – the whole outdoor unit controller, including the wiring, is under
HIGH VOLTAGE!!!
Never open the Outdoor unit before turning off the Power!!!
When turned off, the system is still charged (400V)!!!
It takes about 1 Min. to discharge the system.
Touching the controller before discharging may cause an electrical shock!!!
For safe handling of the controller please refer to section 12.5 below.
12.1 General System Failures and Corrective Actions
No SYMPTOM PROBABLE CAUSE CORRECTIVE ACTION
1.
Indoor unit power supply indicator
(Red LED) does not light up.
No power supply
Check power supply. If OK,
check display and display
wiring. if OK, replace controller
2.
Indoor unit does not respond to remote
control message
Remote control message
not reached the indoor unit
Check remote control batteries,
if OK, check display and display
wiring, if OK, replace display
PCB. If still not OK replace
controller
3.
Indoor unit responds to remote control
message but Operate indicator (Green
LED) does not light up
Problem with display PCB
Replace display PCB.
If still not OK replace controller
4.
Indoor fan does not start (louvers are
opened and Green LED is ON)
Unit in heat mode and coil
is still not warm
Change to cool mode
Outdoor unit is in opposite
mode
Change operation mode
Problem with controller or
capacitor
Change to high speed and
Check power supply to motor is
higher than 130VAC (for triack
controlled motor) or higher than
220VAC for fixed speed motors,
if OK replace capacitor, if not
OK replace controller
5.
Indoor fan works when unit is OFF,
and indoor fan speed is not changed
by remote control command.
Controller problem Replace controller
6. Water leakage from indoor unit
Indoor unit drainage tube is
blocked
Check and open drainage tube
7.
One indoor unit or more are
operating in cool mode with no
capacity, and the other units have
water leaks/freezing problems
The communication
wires of the indoor units
are switched
Check and correct the
communication wires
connection
8.
One indoor or more are operating
in heat mode with a limited
capacity, and the coil on the other
units are very hot.